C.17
C
M-PACT
382 to door
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Minimum clearance
to cassette side.
Fascia centre
Fascia centre
Connected 414
50 Disconnected
35 Test
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
ACB fascia
cut-out dimension
382 to door
Copperwork must be supported within 200mm of breaker connections – busbars or cables.
All connections to be tightened to 50Nm.
Minimum clearance
to cassette side.
Fascia centre
Fascia centre
Connected 414
50 Disconnected
35 Test
The cut-out
dimensions give an
approximate nominal
clearance of 3mm
around ACB fascia.
These sizes are for
guidance and can be
scaled if a different
aperture is required.
ACB fascia
cut-out dimension
Type S - 4 pole - Frame size 2, In = 3200A & 4000A (max)
Type S - 3 pole - Frame size 2, In = 3200A & 4000A (max)
Front Access Connection
Withdrawable Pattern